释义 |
- Acquired Standards International Standards
- RAPIEnet Technology Protocol Stack Structure Embedded dual port switch motion Frame Format Topology Recovery System Flexible Hybrid Structure
- System Diagram Using RAPIEnet
- Others Other international standards in process
- References
{{Advert|date=May 2012}}RAPIEnet | | Protocol Information |
---|
Type of Network | Open Real-time Ethernet | Physical Layer | IEEE 802.3, Ethertype 0x88fe | Network Topology | Ring or Line topology | Device Addressing | DIP switch or hardware/software | Network Configuration | Automatically done by protocol | |
RAPIEnet (Real-time Automation Protocols for Industrial Ethernet) is Korea's first Ethernet international standard for real-time data transmission. - An Ethernet-based industrial networking protocol [1] developed in-house by LSIS guarantees real-time transmission and is registered as an international standard.[1] (IEC 61158-3-21: 2010, IEC 61158-4-21: 2010, IEC 61158-5-21: 2010, IEC 61158-6-21: 2010, IEC 61784-2: 2010, IEC 62439-7)
- An embedded Ethernet switch with two ports enables the network expansion in a daisy chain without the need for an additional external switch, easy installation and wiring reduction.[1]
- With 100Mbit/s/1Gbit/s transmission speed, electrical and optical media can be used together.[1][2]
- Supports transmission modes such as Unicast, Multicast and Broadcast.[1]
- Supports "Store & Forward”and “Cut Through” switching.[1]
Acquired Standards International Standards- IEC 61158-3-21: 2010, Industrial communication networks - Fieldbus specifications - Part 3-21: Data-link layer service definition - Type 21 elements.[3]
- IEC 61158-4-21: 2010, Industrial communication networks - Fieldbus specifications - Part 4-21: Data-link layer protocol specification - Type 21 elements.[4]
- IEC 61158-5-21: 2010, Industrial communication networks - Fieldbus specifications - Part 5-21: Application layer service definition - Type 21 elements.[5]
- IEC 61158-6-21: 2010, Industrial communication networks - Fieldbus specifications - Part 6-21: Application layer protocol specification - Type 21 elements.[6]
- IEC 61784-2: 2010, Industrial communication networks - Profiles - Part 2: Additional fieldbus profiles for real-time networks based on ISO/IEC 8802-3.[7]
- IEC 62439-7, Industrial communication networks - High availability automation networks - Part 7: Ring-based Redundancy Protocol (RRP) [8]
RAPIEnet TechnologyProtocol Stack Structure{{Clear}}Embedded dual port switch motion{{Clear}}- An embedded hardware-based switch is adopted for real-time data transmission.
- With the full-duplex communication support, each node has dual link routes in a ring topology.
{{Clear}}Frame Format{{Clear}}- RAPIEnet Ether type: 0x88FE[9]
Topology{{Clear}}{{Clear}}Recovery System- With an embedded switch and full-duplex, it has dual link routes and communication fault tolerance, enabling fast recovery capabilities.
- Recovery time < 10 ms[4] {{Clear}}{{Clear}}- Transmits signal from Device 1 to Device 3.
- A fault occurs between Device 2 and Device 3.
- Notify the fault from Device 2 to Device 1.
- Transmits signal back from Device 1 to Device 3.
Flexible Hybrid Structure{{Clear}}- Fiber Optics/Copper Media
- Copper: Low installation costs with relatively big noise. - Optics: High installation costs with low noise and relatively long wiring. - Simple and efficient wiring is available by combining the features of two wires that have advantages and disadvantages.
{{Clear}}System Diagram Using RAPIEnet{{Clear}}OthersOther international standards in process- IEC 61784-5-17, Industrial communication networks - Profiles - Part 5-17: Installation of fieldbuses - Installation profiles for CPF 17 (to be registered as an IEC international standard in 2012)[10]
References 1. ^RAPIEnet related articles 2. ^ISO/IEC 8802-3: 2000 3. ^IEC 61158-3-21: 2010 4. ^1 2 3 4 5 6 IEC 61158-4-21: 2010 5. ^IEC 61158-5-21: 2010 6. ^IEC 61158-6-21: 2010 7. ^IEC 61784-2: 2010 8. ^IEC 62439-7{{dead link|date=April 2018 |bot=InternetArchiveBot |fix-attempted=yes }} 9. ^IEEE - Ether type 10. ^IEC 61784-5-17{{dead link|date=April 2018 |bot=InternetArchiveBot |fix-attempted=yes }}
{{Automation protocols}}{{DEFAULTSORT:RAPIEnet}} 1 : Industrial Ethernet |