请输入您要查询的百科知识:

 

词条 Quadrature booster
释义

  1. Method of operation

  2. Arrangement

  3. Illustration of effect

  4. See also

  5. References

  6. External links

{{redirect|Phase-shifter|the microwave network module|Phase shift module}}

A phase angle regulating transformer, phase angle regulator (PAR, American usage), phase-shifting transformer, phase shifter (West coast American usage), or quadrature booster (quad booster, British usage), is a specialised form of transformer used to control the flow of real power on three-phase electric transmission networks.

For an alternating current transmission line, power flow through the line is proportional to the sine of the difference in the phase angle of the voltage between the transmitting end and the receiving end of the line.[1] Where parallel circuits with different capacities exist between two points in a transmission grid (for example, an overhead line and an underground cable), direct manipulation of the phase angle allows control of the division of power flow between the paths, preventing overload.[2] Quadrature boosters thus provide a means of relieving overloads on heavily laden circuits and re-routing power via more favorable paths.

Alternately, where an interchange partner is intentionally causing significant "inadvertent energy" to flow through an unwilling interchange partner's system, the unwilling partner may threaten to install a phase shifter to prevent such "inadvertent energy", with the unwilling partner's tactical objective being the improvement of its own system's stability at the expense of the other system's stability. As power system stability—hence reliability—is really a regional or national operational objective, the threat to install a phase shifter is usually sufficient to cause the offending system to implement the required changes to its own system to greatly reduce or eliminate the "inadvertent energy" flowing through the offended system.

The capital cost of a quadrature booster can be high: as much as four to six million GBP (6–9 million USD) for a unit rated over 2 GVA. However, the utility to transmission system operators in flexibility and speed of operation, and, more particularly, facilitating economic dispatch of generation, can soon recover the cost of ownership.

Method of operation

By means of a voltage derived from the supply that is first phase-shifted by 90° (hence is in quadrature), and then re-applied to it, a phase angle is developed across the quadrature booster. It is this induced phase angle that affects the flow of power through specified circuits.

Arrangement

A quadrature booster typically consists of two separate transformers: a shunt unit and a series unit. The shunt unit has its windings connected across the phases, so it produces output voltages shifted by 90° with respect to the supply. Its output is then applied as input to the series unit, which, because its secondary winding is in series with the main circuit, adds the phase-shifted component. The overall output voltage is hence the vector sum of the supply voltage and the 90° quadrature component.

Tap connections on the shunt unit allow the magnitude of the quadrature component to be controlled, and thus the magnitude of the phase shift across the quadrature booster. The flow on the circuit containing the quadrature booster may be increased (boost tapping) or reduced (buck tapping). Subject to system conditions, the flow may even be bucked enough to completely reverse from its neutral-tap direction.

Illustration of effect

The one-line diagram below shows the effect of tapping a quadrature booster on a notional 100 MW generator-load system with two parallel transmission lines, one of which features a quadrature booster (shaded grey) with a tap range of 1 to 19.

In the left-hand image, the quadrature booster is at its centre tap position of 10 and has a phase angle of 0°. It thus does not affect the power flow through its circuit and both lines are equally loaded at 50 MW. The right-hand image shows the same network with the quadrature booster tapped down so as to buck the power flow. The resulting negative phase angle has diverted 23 MW of loading onto the parallel circuit, while the total load supplied is unchanged at 100 MW. (Note that the values used here are hypothetical; the actual phase angle and transfer in load would depend upon the parameters of the quadrature booster and the transmission lines.)

The intended effect is opposite: equalizing power on lines where naturally one would be heavily loaded and one would be lightly loaded.

See also

  • Induction regulator
  • Variable-frequency transformer

References

Bibliography
  • {{cite book | author=Weedy, D. | title=Electrical Power Systems |publisher=Wiley| year=1988 | isbn=978-0-471-97677-6}}
  • {{cite book | author=Guile, A. Paterson, W. | title=Electrical Power Systems vol 1 |publisher=Pergamon | year=1977 | isbn=978-0-08-021729-1}}
Notes
1. ^The "equal area criteria" for power system stability requires that this angle be less than 90 degrees, so for practical purposes this angle will be measurably less than 90 degrees.
2. ^{{Citation |first=B. M. |last=Weedy |title=Electric Power Systems |edition=Second |publisher=John Wiley and Sons |place=London |year=1972 |isbn=978-0-471-92445-6 |pages=127–128}}

External links

  • Phase Shifting Transformers: Principles and Applications (overview article and a case study)
  • [https://books.google.com/books?id=y33w-glgIEYC&pg=PA214&lpg=PA214&dq=Phase+Transformers:+Principles+and+Applications&source=bl&ots=TdQa_6xDRc&sig=oTyqHspu42f7ZHOl3rHdV9ficV8&hl=en&sa=X&ei=ysLaUo-aNcWvsQSDhoHoDQ&ved=0CGwQ6AEwCQ#v=onepage&q=Phase%20Shifting%20Transformers%3A%20Principles%20and%20Applications&f=false Phase Shifting Transformers: Principles and Applications] (Book by John Winders, CRC Press, Apr 12, 2002)
{{Electric transformers}}

1 : Electric transformers

随便看

 

开放百科全书收录14589846条英语、德语、日语等多语种百科知识,基本涵盖了大多数领域的百科知识,是一部内容自由、开放的电子版国际百科全书。

 

Copyright © 2023 OENC.NET All Rights Reserved
京ICP备2021023879号 更新时间:2024/11/13 14:28:04