A cooling tower is a heat rejection device that rejects waste heat to the atmosphere through the cooling of a water stream to a lower temperature. Cooling towers may either use the evaporation of water to remove process heat and cool the working fluid to near the wet-bulb air temperature or, in the case of closed circuit dry cooling towers, rely solely on air to cool the working fluid to near the dry-bulb air temperature. Common applications include cooling the circulating water used in oil refineries, petrochemical and other chemical plants, thermal power stations and HVAC systems for cooling buildings. The classification is based on the type of air induction into the tower: the main types of cooling towers are natural draft and induced draft cooling towers. Cooling towers vary in size from small roof-top units to very large hyperboloid structures (as in the adjacent image) that can be up to {{convert|200|m|ft}} tall and {{convert|100|m|ft}} in diameter, or rectangular structures that can be over {{convert|40|m|ft}} tall and {{convert|80|m|ft}} long. The hyperboloid cooling towers are often associated with nuclear power plants,[1] although they are also used in some coal-fired plants and to some extent in some large chemical and other industrial plants. Although these large towers are very prominent, the vast majority of cooling towers are much smaller, including many units installed on or near buildings to discharge heat from air conditioning. HistoryCooling towers originated in the 19th century through the development of condensers for use with the steam engine.[2] Condensers use relatively cool water, via various means, to condense the steam coming out of the cylinders or turbines. This reduces the back pressure, which in turn reduces the steam consumption, and thus the fuel consumption, while at the same time increasing power and recycling boiler-water.[3] However the condensers require an ample supply of cooling water, without which they are impractical.[4][4] The consumption of cooling water by inland processing and power plants is estimated to reduce power availability for the majority of thermal power plants by 2040–2069.[5] While water usage is not an issue with marine engines, it forms a significant limitation for many land-based systems. By the turn of the 20th century, several evaporative methods of recycling cooling water were in use in areas lacking an established water supply, as well as in urban locations where municipal water mains may not be of sufficient supply; reliable in times of demand; or otherwise adequate to meet cooling needs.[2][4] In areas with available land, the systems took the form of cooling ponds; in areas with limited land, such as in cities, they took the form of cooling towers.[6][10] These early towers were positioned either on the rooftops of buildings or as free-standing structures, supplied with air by fans or relying on natural airflow.[6][7] An American engineering textbook from 1911 described one design as "a circular or rectangular shell of light plate—in effect, a chimney stack much shortened vertically (20 to 40 ft. high) and very much enlarged laterally. At the top is a set of distributing troughs, to which the water from the condenser must be pumped; from these it trickles down over "mats" made of wooden slats or woven wire screens, which fill the space within the tower."[7] A hyperboloid cooling tower was patented by the Dutch engineers Frederik van Iterson and Gerard Kuypers in 1918.[8] The first hyperboloid cooling towers were built in 1918 near Heerlen. The first ones in the United Kingdom were built in 1924 at Lister Drive power station in Liverpool, England, to cool water used at a coal-fired electrical power station.[9] Classification by useHeating, ventilation and air conditioning (HVAC){{main|HVAC}}An HVAC (heating, ventilating, and air conditioning) cooling tower is used to dispose of ("reject") unwanted heat from a chiller. Water-cooled chillers are normally more energy efficient than air-cooled chillers due to heat rejection to tower water at or near wet-bulb temperatures. Air-cooled chillers must reject heat at the higher dry-bulb temperature, and thus have a lower average reverse-Carnot cycle effectiveness. In areas with a hot climate, large office buildings, hospitals, and schools typically use one or more cooling towers as part of their air conditioning systems. Generally, industrial cooling towers are much larger than HVAC towers. HVAC use of a cooling tower pairs the cooling tower with a water-cooled chiller or water-cooled condenser. A ton of air-conditioning is defined as the removal of 12,000 BTU/hour (3500 W). The equivalent ton on the cooling tower side actually rejects about 15,000 BTU/hour (4400 W) due to the additional waste heat-equivalent of the energy needed to drive the chiller's compressor. This equivalent ton is defined as the heat rejection in cooling 3 US gallons/minute (1,500 pound/hour) of water 10 °F (6 °C), which amounts to 15,000 BTU/hour, assuming a chiller coefficient of performance (COP) of 4.0.[10] This COP is equivalent to an energy efficiency ratio (EER) of 14. Cooling towers are also used in HVAC systems that have multiple water source heat pumps that share a common piping water loop. In this type of system, the water circulating inside the water loop removes heat from the condenser of the heat pumps whenever the heat pumps are working in the cooling mode, then the externally mounted cooling tower is used to remove heat from the water loop and reject it to the atmosphere. By contrast, when the heat pumps are working in heating mode, the condensers draw heat out of the loop water and reject it into the space to be heated. When the water loop is being used primarily to supply heat to the building, the cooling tower is normally shut down (and may be drained or winterized to prevent freeze damage), and heat is supplied by other means, usually from separate boilers. Industrial cooling towersIndustrial cooling towers can be used to remove heat from various sources such as machinery or heated process material. The primary use of large, industrial cooling towers is to remove the heat absorbed in the circulating cooling water systems used in power plants, petroleum refineries, petrochemical plants, natural gas processing plants, food processing plants, semi-conductor plants, and for other industrial facilities such as in condensers of distillation columns, for cooling liquid in crystallization, etc.[11] The circulation rate of cooling water in a typical 700 MW coal-fired power plant with a cooling tower amounts to about 71,600 cubic metres an hour (315,000 US gallons per minute)[12] and the circulating water requires a supply water make-up rate of perhaps 5 percent (i.e., 3,600 cubic metres an hour). If that same plant had no cooling tower and used once-through cooling water, it would require about 100,000 cubic metres an hour[13] A large cooling water intake typically kills millions of fish and larvae annually, as the organisms are impinged on the intake screens.[14] A large amount of water would have to be continuously returned to the ocean, lake or river from which it was obtained and continuously re-supplied to the plant. Furthermore, discharging large amounts of hot water may raise the temperature of the receiving river or lake to an unacceptable level for the local ecosystem. Elevated water temperatures can kill fish and other aquatic organisms (see thermal pollution), or can also cause an increase in undesirable organisms such as invasive species of zebra mussels or algae. A cooling tower serves to dissipate the heat into the atmosphere instead and wind and air diffusion spreads the heat over a much larger area than hot water can distribute heat in a body of water. Evaporative cooling water cannot be used for subsequent purposes (other than rain somewhere), whereas surface-only cooling water can be re-used. Some coal-fired and nuclear power plants located in coastal areas do make use of once-through ocean water. But even there, the offshore discharge water outlet requires very careful design to avoid environmental problems. Petroleum refineries also have very large cooling tower systems. A typical large refinery processing 40,000 metric tonnes of crude oil per day ({{convert|300000|oilbbl}} per day) circulates about 80,000 cubic metres of water per hour through its cooling tower system. The world's tallest cooling tower is the {{convert|202|m|ft}} tall cooling tower of Kalisindh Thermal Power Station in Jhalawar, Rajasthan, India.[15] Classification by buildPackage typeThese types of cooling towers are factory preassembled, and can be simply transported on trucks, as they are compact machines. The capacity of package type towers is limited and, for that reason, they are usually preferred by facilities with low heat rejection requirements such as food processing plants, textile plants, some chemical processing plants, or buildings like hospitals, hotels, malls, automotive factories etc. Due to their frequent use in or near residential areas, sound level control is a relatively more important issue for package type cooling towers. Field erection typeFacilities such as power plants, steel processing plants, petroleum refineries, or petrochemical plants usually install field erected type cooling towers due to their greater capacity for heat rejection. Field erected towers are usually much larger in size compared to the package type cooling towers. A typical field erected cooling tower has a pultruded fiber-reinforced plastic (FRP) structure, FRP cladding, a mechanical unit for air draft, drift eliminator, and fill. Heat transfer methodsWith respect to the heat transfer mechanism employed, the main types are:
In a wet cooling tower (or open circuit cooling tower), the warm water can be cooled to a temperature lower than the ambient air dry-bulb temperature, if the air is relatively dry (see dew point and psychrometrics). As ambient air is drawn past a flow of water, a small portion of the water evaporates, and the energy required to evaporate that portion of the water is taken from the remaining mass of water, thus reducing its temperature. Approximately 970 BTU of heat energy is absorbed for each pound of evaporated water (2 MJ/kg). Evaporation results in saturated air conditions, lowering the temperature of the water processed by the tower to a value close to wet-bulb temperature, which is lower than the ambient dry-bulb temperature, the difference determined by the initial humidity of the ambient air. To achieve better performance (more cooling), a medium called fill is used to increase the surface area and the time of contact between the air and water flows. Splash fill consists of material placed to interrupt the water flow causing splashing. Film fill is composed of thin sheets of material (usually PVC) upon which the water flows. Both methods create increased surface area and time of contact between the fluid (water) and the gas (air), to improve heat transfer. Air flow generation methodsWith respect to drawing air through the tower, there are three types of cooling towers:
Hyperboloid (sometimes incorrectly known as hyperbolic) cooling towers have become the design standard for all natural-draft cooling towers because of their structural strength and minimum usage of material. The hyperboloid shape also aids in accelerating the upward convective air flow, improving cooling efficiency. These designs are popularly associated with nuclear power plants. However, this association is misleading, as the same kind of cooling towers are often used at large coal-fired power plants as well. Conversely, not all nuclear power plants have cooling towers, and some instead cool their heat exchangers with lake, river or ocean water. Thermal efficiencies up to 92% have been observed in hybrid cooling towers.[16] Categorization by air-to-water flowCrossflowTypically lower initial and long-term cost, mostly due to pump requirements. Crossflow is a design in which the air flow is directed perpendicular to the water flow (see diagram at left). Air flow enters one or more vertical faces of the cooling tower to meet the fill material. Water flows (perpendicular to the air) through the fill by gravity. The air continues through the fill and thus past the water flow into an open plenum volume. Lastly, a fan forces the air out into the atmosphere. A distribution or hot water basin consisting of a deep pan with holes or nozzles in its bottom is located near the top of a crossflow tower. Gravity distributes the water through the nozzles uniformly across the fill material. Advantages of the crossflow design:
Disadvantages of the crossflow design:
CounterflowIn a counterflow design, the air flow is directly opposite to the water flow (see diagram at left). Air flow first enters an open area beneath the fill media, and is then drawn up vertically. The water is sprayed through pressurized nozzles near the top of the tower, and then flows downward through the fill, opposite to the air flow. Advantages of the counterflow design:
Disadvantages of the counterflow design:
Common aspectsCommon aspects of both designs:
Both crossflow and counterflow designs can be used in natural draft and in mechanical draft cooling towers. Wet cooling tower material balanceQuantitatively, the material balance around a wet, evaporative cooling tower system is governed by the operational variables of make-up volumetric flow rate, evaporation and windage losses, draw-off rate, and the concentration cycles.[17][18] In the adjacent diagram, water pumped from the tower basin is the cooling water routed through the process coolers and condensers in an industrial facility. The cool water absorbs heat from the hot process streams which need to be cooled or condensed, and the absorbed heat warms the circulating water (C). The warm water returns to the top of the cooling tower and trickles downward over the fill material inside the tower. As it trickles down, it contacts ambient air rising up through the tower either by natural draft or by forced draft using large fans in the tower. That contact causes a small amount of the water to be lost as windage/drift (W) and some of the water (E) to evaporate. The heat required to evaporate the water is derived from the water itself, which cools the water back to the original basin water temperature and the water is then ready to recirculate. The evaporated water leaves its dissolved salts behind in the bulk of the water which has not been evaporated, thus raising the salt concentration in the circulating cooling water. To prevent the salt concentration of the water from becoming too high, a portion of the water is drawn off/blown down (D) for disposal. Fresh water make-up (M) is supplied to the tower basin to compensate for the loss of evaporated water, the windage loss water and the draw-off water. Using these flow rates and concentration dimensional units:
A water balance around the entire system is then:[18] M = E + D + W Since the evaporated water (E) has no salts, a chloride balance around the system is:[18] and, therefore:[18] From a simplified heat balance around the cooling tower:
Windage (or drift) losses (W) is the amount of total tower water flow that is entrained in the flow of air to the atmosphere. From large-scale industrial cooling towers, in the absence of manufacturer's data, it may be assumed to be: W = 0.3 to 1.0 percent of C for a natural draft cooling tower without windage drift eliminators W = 0.1 to 0.3 percent of C for an induced draft cooling tower without windage drift eliminators W = about 0.005 percent of C (or less) if the cooling tower has windage drift eliminators W = about 0.0005 percent of C (or less) if the cooling tower has windage drift eliminators and uses sea water as make-up water. Cycles of concentrationCycle of concentration represents the accumulation of dissolved minerals in the recirculating cooling water. Discharge of draw-off (or blowdown) is used principally to control the buildup of these minerals. The chemistry of the make-up water, including the amount of dissolved minerals, can vary widely. Make-up waters low in dissolved minerals such as those from surface water supplies (lakes, rivers etc.) tend to be aggressive to metals (corrosive). Make-up waters from ground water supplies (such as wells) are usually higher in minerals, and tend to be scaling (deposit minerals). Increasing the amount of minerals present in the water by cycling can make water less aggressive to piping; however, excessive levels of minerals can cause scaling problems. Concentration cycles in the majority of cooling towers usually range from 3 to 7. In the United States, many water supplies use well water which has significant levels of dissolved solids. On the other hand, one of the largest water supplies, for New York City, has a surface rainwater source quite low in minerals; thus cooling towers in that city are often allowed to concentrate to 7 or more cycles of concentration. Since higher cycles of concentration represent less make-up water, water conservation efforts may focus on increasing cycles of concentration.[19] Highly treated recycled water may be an effective means of reducing cooling tower consumption of potable water, in regions where potable water is scarce.[20] MaintenanceSurfaces with any visible biofilm (i.e., slime) should be cleaned. Disinfectant and other chemical levels in cooling towers and hot tubs should be continuously maintained and regularly monitored.[21] Regular checks of water quality (specifically the aerobic bacteria levels) using dipslides should be taken as the presence of other organisms can support legionella by producing the organic nutrients that it needs to thrive.[22] Water treatment{{see also|Industrial water treatment}}Besides treating the circulating cooling water in large industrial cooling tower systems to minimize scaling and fouling, the water should be filtered to remove particulates, and also be dosed with biocides and algaecides to prevent growths that could interfere with the continuous flow of the water.[17] Under certain conditions, a biofilm of micro-organisms such as bacteria, fungi and algae can grow very rapidly in the cooling water, and can reduce the heat transfer efficiency of the cooling tower. Biofilm can be reduced or prevented by using chlorine or other chemicals. A normal industrial practice is to use two biocides, such as oxidizing and non-oxidizing types to complement each other's strengths and weaknesses, and to ensure a broader spectrum of attack. In most cases, a continual low level oxidizing biocide is used, then alternating to a periodic shock dose of non-oxidizing biocides.[23] Legionnaires' disease{{further|Legionellosis|Legionella}}Another very important reason for using biocides in cooling towers is to prevent the growth of Legionella, including species that cause legionellosis or Legionnaires' disease, most notably L. pneumophila,[24] or Mycobacterium avium.[25] The various Legionella species are the cause of Legionnaires' disease in humans and transmission is via exposure to aerosols—the inhalation of mist droplets containing the bacteria. Common sources of Legionella include cooling towers used in open recirculating evaporative cooling water systems, domestic hot water systems, fountains, and similar disseminators that tap into a public water supply. Natural sources include freshwater ponds and creeks.[26][27] French researchers found that Legionella bacteria travelled up to {{convert|6|km|mi}} through the air from a large contaminated cooling tower at a petrochemical plant in Pas-de-Calais, France. That outbreak killed 21 of the 86 people who had a laboratory-confirmed infection.[28] Drift (or windage) is the term for water droplets of the process flow allowed to escape in the cooling tower discharge. Drift eliminators are used in order to hold drift rates typically to 0.001–0.005% of the circulating flow rate. A typical drift eliminator provides multiple directional changes of airflow to prevent the escape of water droplets. A well-designed and well-fitted drift eliminator can greatly reduce water loss and potential for Legionella or water treatment chemical exposure. The CDC does not recommend that health-care facilities regularly test for the Legionella pneumophila bacteria. Scheduled microbiologic monitoring for Legionella remains controversial because its presence is not necessarily evidence of a potential for causing disease. The CDC recommends aggressive disinfection measures for cleaning and maintaining devices known to transmit Legionella, but does not recommend regularly-scheduled microbiologic assays for the bacteria. However, scheduled monitoring of potable water within a hospital might be considered in certain settings where persons are highly susceptible to illness and mortality from Legionella infection (e.g. hematopoietic stem cell transplantation units, or solid organ transplant units). Also, after an outbreak of legionellosis, health officials agree that monitoring is necessary to identify the source and to evaluate the efficacy of biocides or other prevention measures.[29] Studies have found Legionella in 40% to 60% of cooling towers.[30] Terminology{{anchor |Windage|Drift}}
Fog productionUnder certain ambient conditions, plumes of water vapor (fog) can be seen rising out of the discharge from a cooling tower, and can be mistaken as smoke from a fire. If the outdoor air is at or near saturation, and the tower adds more water to the air, saturated air with liquid water droplets can be discharged, which is seen as fog. This phenomenon typically occurs on cool, humid days, but is rare in many climates. Fog and clouds associated with cooling towers can be described as homogenitus, as with other clouds of man-made origin, such as contrails and ship tracks.[34] This phenomenon can be prevented by decreasing the relative humidity of the saturated discharge air. For that purpose, in hybrid towers, saturated discharge air is mixed with heated low relative humidity air. Some air enters the tower above drift eliminator level, passing through heat exchangers. The relative humidity of the dry air is even more decreased instantly as being heated while entering the tower. The discharged mixture has a relatively lower relative humidity and the fog is invisible. Salt emission pollutionWhen wet cooling towers with seawater make-up are installed in various industries located in or near coastal areas, the drift of fine droplets emitted from the cooling towers contain nearly 6% sodium chloride which deposits on the nearby land areas. This deposition of sodium salts on the nearby agriculture/vegetative lands can convert them into sodic saline or sodic alkaline soils depending on the nature of the soil and enhance the sodicity of ground and surface water. The salt deposition problem from such cooling towers aggravates where national pollution control standards are not imposed or not implemented to minimize the drift emissions from wet cooling towers using seawater make-up.[35] Respirable suspended particulate matter, of less than 10 micrometers (µm) in size, can be present in the drift from cooling towers. Larger particles above 10 µm in size are generally filtered out in the nose and throat via cilia and mucus but particulate matter smaller than 10 µm, referred to as PM10, can settle in the bronchi and lungs and cause health problems. Similarly, particles smaller than 2.5 µm, (PM2.5), tend to penetrate into the gas exchange regions of the lung, and very small particles (less than 100 nanometers) may pass through the lungs to affect other organs. Though the total particulate emissions from wet cooling towers with fresh water make-up is much less, they contain more PM10 and PM2.5 than the total emissions from wet cooling towers with sea water make-up. This is due to lesser salt content in fresh water drift (below 2,000 ppm) compared to the salt content of sea water drift (60,000 ppm).[35]Use as a flue-gas stackAt some modern power stations equipped with flue gas purification, such as the Großkrotzenburg Power Station and the Rostock Power Station, the cooling tower is also used as a flue-gas stack (industrial chimney), thus saving the cost of a separate chimney structure. At plants without flue gas purification, problems with corrosion may occur, due to reactions of raw flue gas with water to form acids. Sometimes, natural draft cooling towers are constructed with structural steel in place of concrete (RCC) when the construction time of natural draft cooling tower is exceeding the construction time of the rest of the plant or the local soil is of poor strength to bear the heavy weight of RCC cooling towers or cement prices are higher at a site to opt for cheaper natural draft cooling towers made of structural steel. Operation in freezing weatherSome cooling towers (such as smaller building air conditioning systems) are shut down seasonally, drained, and winterized to prevent freeze damage. During the winter, other sites continuously operate cooling towers with {{convert|4|°C|°F|abbr=on}} water leaving the tower. Basin heaters, tower draindown, and other freeze protection methods are often employed in cold climates. Operational cooling towers with malfunctions can freeze during very cold weather. Typically, freezing starts at the corners of a cooling tower with a reduced or absent heat load. Severe freezing conditions can create growing volumes of ice, resulting in increased structural loads which can cause structural damage or collapse. To prevent freezing, the following procedures are used:
Fire hazardCooling towers constructed in whole or in part of combustible materials can support internal fire propagation. Such fires can become very intense, due to the high surface-volume ratio of the towers, and fires can be further intensified by natural convection or fan-assisted draft. The resulting damage can be sufficiently severe to require the replacement of the entire cell or tower structure. For this reason, some codes and standards[38] recommend that combustible cooling towers be provided with an automatic fire sprinkler system. Fires can propagate internally within the tower structure when the cell is not in operation (such as for maintenance or construction), and even while the tower is in operation, especially those of the induced-draft type, because of the existence of relatively dry areas within the towers.[39] Structural stabilityBeing very large structures, cooling towers are susceptible to wind damage, and several spectacular failures have occurred in the past. At Ferrybridge power station on 1 November 1965, the station was the site of a major structural failure, when three of the cooling towers collapsed owing to vibrations in {{convert|85|mi/h|km/h|abbr=on}} winds.{{Citation needed|date=June 2017}} Although the structures had been built to withstand higher wind speeds, the shape of the cooling towers caused westerly winds to be funnelled into the towers themselves, creating a vortex. Three out of the original eight cooling towers were destroyed, and the remaining five were severely damaged. The towers were later rebuilt and all eight cooling towers were strengthened to tolerate adverse weather conditions. Building codes were changed to include improved structural support, and wind tunnel tests were introduced to check tower structures and configuration.{{Citation needed|date=June 2017}} See also{{div col|colwidth=30em}}
References1. ^CleanEnergy Footprints (cleanenergy.org). Identifying Nuclear Reactors in Google Earth Retrieved 5/19/2014 2. ^1 {{cite book |author=International Correspondence Schools |date=1902 |title=A Textbook on Steam Engineering |publisher=International Textbook Co. |location=Scranton, Pa. |at=33–34 of Section 29:"Condensers" |url=https://archive.org/details/textbookonsteame04inteiala}} 3. ^{{cite book |editor-last=Croft |editor-first=Terrell |date=1922 |title=Steam-Engine Principles and Practice |publisher=McGraw-Hill |location=New York |pages=283–286 |url=https://archive.org/details/steamengineprinc00crofrich}} 4. ^1 {{cite journal |last=Watson |first=Egbert P. |date=1 Jan 1906 |title=Power plant and allied industries |journal=The Engineer (with Which is Incorporated Steam Engineering) |volume=43 |issue=1 |pages=69–72 |publisher=Taylor Publishing Co. |location=Chicago |url=https://books.google.com/books?id=cKUiAQAAMAAJ}} 5. ^{{cite journal |last1=van Vliet |first1=Michelle T. H. |last2=Wiberg |first2=David |last3=Leduc |first3=Sylvain |last4=Riahi |first4=Keywan |date=4 January 2016 |title=Power-generation system vulnerability and adaptation to changes in climate and water resources |journal=Nature Climate Change |volume=6 |issue=4 |pages=375–380 |doi=10.1038/nclimate2903 |url=http://www.nature.com/nclimate/journal/v6/n4/full/nclimate2903.html |accessdate=28 March 2016}} 6. ^1 2 {{cite book |last=Heck |first=Robert Culbertson Hays |date=1911 |title=The Steam Engine and Turbine: A Text-Book for Engineering Colleges |publisher=D. Van Nostrand |location=New York |pages=569–570 |url=https://archive.org/details/steamengineturbi00heck}} 7. ^1 2 {{cite book |last=Snow |first=Walter B. |date=1908 |title=The Steam Engine: A Practical Guide to the Construction, Operation, and care of Steam Engines, Steam Turbines, and Their Accessories |publisher=American School of Correspondence |location=Chicago |pages=43–46 |url=https://archive.org/details/steamenginepract00amerrich}} 8. ^UK Patent No. 108,863 9. ^[https://books.google.com/books?id=p-IDAAAAMBAJ&pg=PA201&dq=Popular+Science+1930+plane+%22Popular+Mechanics%22&hl=en&ei=kHFkTvrWBK3G0AHHlemCCg&sa=X&oi=book_result&ct=result&resnum=9&sqi=2&ved=0CEsQ6AEwCA#v=onepage&q&f=true "Power Plant Cooling Towers Like Big Milk Bottle" Popular Mechanics, February 1930] bottom-left of pg 201 10. ^{{cite book|last1=Cheremisinoff|first1=Nicholas|title=Handbook of Chemical Processing Equipment|date=2000|publisher=Butterworth-Heinemann|isbn=9780080523828|page=69}} 11. ^{{Cite report |title=Profile of the Fossil Fuel Electric Power Generation Industry |url=http://www.epa.gov/compliance/resources/publications/assistance/sectors/notebooks/fossil.html |author=U.S. Environmental Protection Agency (EPA). |year= 1997 |publisher= Washington, D.C |accessdate= }} Document No. EPA/310-R-97-007. p. 79. 12. ^Cooling System Retrofit Costs EPA Workshop on Cooling Water Intake Technologies, John Maulbetsch, Maulbetsch Consulting, May 2003 13. ^Thomas J. Feeley, III, Lindsay Green, James T. Murphy, Jeffrey Hoffmann, and Barbara A. Carney (2005). "Department of Energy/Office of Fossil Energy’s Power Plant Water Management R&D Program." {{webarchive|url=https://web.archive.org/web/20070927104349/http://204.154.137.14/technologies/coalpower/ewr/pubs/IEP_Power_Plant_Water_R%26D_Final_1.pdf |date=27 September 2007 }} U.S. Department of Energy, July 2005. 14. ^The Indian Point Energy Center cooling system kills over a billion fish eggs and larvae annually. {{cite news |last=McGeehan |first=Patrick |date=2015-05-12 |title=Fire Prompts Renewed Calls to Close the Indian Point Nuclear Plant |url=https://www.nytimes.com/2015/05/13/nyregion/fire-prompts-renewed-calls-to-close-the-indian-point-nuclear-plant.html |newspaper=New York Times}} 15. ^Comansa Jie builds the world’s highest cooling towers 16. ^{{Cite journal|last=Gul|first=S.|date=2015-06-18|title=Optimizing the performance of Hybrid: Induced-Forced Draft Cooling Tower|url=http://www.piche.org.pk/journal/index.php?journal=jpiche&page=article&op=view&path%5B%5D=192|journal=Journal of the Pakistan Institute of Chemical Engineers|language=en|volume=43|issue=2|issn=1813-4092}} 17. ^1 {{cite book | author=Beychok, Milton R. | title=Aqueous Wastes from Petroleum and Petrochemical Plants |edition=1st | publisher=John Wiley and Sons | year=1967|id=[[Library of Congress Control Number|| lccn=67019834]] | title-link=Aqueous Wastes from Petroleum and Petrochemical Plants }} (available in many university libraries) 18. ^1 2 3 {{cite journal| author=Milton R. Beychok|date=October 1952|title=How To Calculate Cooling Tower Control Variables|journal= Petroleum Processing| volume=|issue=|pages=1452–1456}} 19. ^{{cite web |url = http://energy.gov/eere/femp/best-management-practice-cooling-tower-management |title = Best Management Practice Cooling Tower Management |publisher = Department of Energy |date = 30 April 2005 |website = Energy.gov |accessdate= 16 June 2014 }} 20. ^{{cite journal | last = San Diego County Water Authority | date = July 2009 | title = Technical Information for Cooling Towers Using Recycled Water | url = http://www.sdcwa.org/sites/default/files/files/water-management/recycled/techinfo-cooling-towers.pdf | website = www.sdcwa.org | publisher = San Diego County Water Authority | accessdate = 18 June 2014 }} 21. ^{{cite web|url =https://www.cdc.gov/legionella/downloads/toolkit.pdf |title=Developing a Water Management Program to Reduce Legionella Growth & Spread in Buildings: A Practical Guide to Implementing Industry Standards | publisher =CDC |date = 5 June 2017|page= 13 {17 of 32}}} 22. ^{{Cite web|url=https://dip-slides.com/cooling-water/69-cooling-water-dipslides-box-of-10.html|title=Cooling Water Dipslides (Box of 10) - Dip-slides.com|website=Dip-slides.com|language=en-us|access-date=2017-07-05}} 23. ^{{Cite web |url=http://www.bvwater.co.uk/cooling-water-system-chemicals/ |title=B & V Group, Cooling Water System Chemical Range, Non-Oxidising Biocides |access-date=14 December 2016 |archive-url=https://web.archive.org/web/20160829064240/http://www.bvwater.co.uk/cooling-water-system-chemicals/#.WFFOPqZ4e7k |archive-date=29 August 2016 |dead-url=yes |df=dmy-all }} 24. ^{{cite book|author=Ryan K.J.; Ray C.G. (editors)|title=Sherris Medical Microbiology|edition=4th|publisher=McGraw Hill|year=2004|isbn=978-0-8385-8529-0}} 25. ^Centers for Disease Control and Prevention – Emerging Infectious Diseases (page 495) 26. ^{{cite journal|last1=Cunha|first1=BA|last2=Burillo|first2=A|last3=Bouza|first3=E|title=Legionnaires' disease.|journal=Lancet|date=23 January 2016|volume=387|issue=10016|pages=376–85|pmid=26231463|doi=10.1016/s0140-6736(15)60078-2}} 27. ^{{cite web|title=Legionella (Legionnaires' Disease and Pontiac Fever) About the Disease|url=https://www.cdc.gov/legionella/about/index.html|website=CDC|accessdate=17 June 2017 |date=26 January 2016}} 28. ^[https://web.archive.org/web/20080922134426/http://www.medscape.com/viewarticle/521680 Airborne Legionella May Travel Several Kilometres] (access requires free registration) 29. ^[https://www.cdc.gov/hicpac/pdf/guidelines/eic_in_HCF_03.pdf CDC Guidelines for Environmental Infection Control in Health-Care Facilities, pages 223 & 224, Water Sampling Strategies and Culture Techniques for Detecting Legionellae] 30. ^Cooling Tower Institute, July 2008. Page 5 of 12, column 1, paragraph 3. Most professional and government agencies do not recommend testing for Legionella bacteria on a routine basis. 31. ^{{citation | author=William H Clark | year=1997 | title=Retrofitting for energy conservation | publisher=McGraw-Hill Professional | isbn=978-0-07-011920-8 | page=66 }} 32. ^{{citation | author=Institute of Industrial Engineers 1981– | year=1982 | title=Proceedings, Volume 1982 | publisher=Institute of Industrial Engineers/American Institute of Industrial Engineers | page=101 }} 33. ^{{citation | last=Mathie | first=Alton J. | year=1998 | title=Chemical treatment for cooling water | publisher=Fairmont Press | isbn=978-0-88173-253-5 | page=86 }} 34. ^{{cite news|last1=Sutherland|first1=Scott|title=Cloud Atlas leaps into 21st century with 12 new cloud types|url=https://www.theweathernetwork.com/news/articles/cloud-atlas-leaps-into-21st-century-with-12-new-cloud-types/80685/|accessdate=24 March 2017|work=The Weather Network|agency=Pelmorex Media|date=23 March 2017}} 35. ^1 Wet Cooling Tower Guidance For Particulate Matter, Environment Canada, Retrieved on 2013-01-29 36. ^SPX Cooling Technologies MARLEY, Cooling Tower Fundamentals Page 73 (75 of 119) Column 2, Last Paragraph 37. ^{{cite web |url= http://spxcooling.com/pdf/H-003B.pdf |title= SPX Cooling Technologies: Operating Cooling Towers in Freezing Weather |deadurl= yes |archiveurl= https://web.archive.org/web/20070927151339/http://spxcooling.com/pdf/H-003B.pdf |archivedate= 27 September 2007 |df= dmy-all }} {{small|(1.45 MB)}} 38. ^National Fire Protection Association (NFPA). NFPA 214, Standard on Water-Cooling Towers. 39. ^NFPA 214, Standard on Water-Cooling Towers. Section A1.1 External links{{Prone to spam|date=March 2013}}{{Z148}}{{Commons}}